Superheat Formula:
From: | To: |
Superheat refers to the excess temperature in refrigerant line after evaporator. It represents the temperature rise of refrigerant vapor above its saturation temperature at a given pressure, measured at the compressor suction line.
The calculator uses the superheat formula:
Where:
Explanation: Superheat ensures that only vapor (no liquid) enters the compressor, preventing compressor damage and optimizing system efficiency.
Details: Proper superheat is critical for compressor protection and system efficiency. Too low superheat can cause liquid refrigerant to enter the compressor (liquid slugging), while too high superheat reduces system capacity and efficiency.
Tips: Enter actual line temperature and saturation temperature in the same units (Celsius or Fahrenheit). Ensure measurements are taken at the compressor suction line with accurate temperature and pressure gauges.
Q1: What is the ideal superheat range for compressors?
A: Typically 5-15°C (10-20°F) at the compressor, but always refer to manufacturer specifications for specific equipment.
Q2: How do I measure saturation temperature?
A: Use a pressure gauge to measure suction pressure, then convert to saturation temperature using refrigerant pressure-temperature charts.
Q3: What causes high superheat?
A: Low refrigerant charge, restricted metering device, dirty evaporator coils, or airflow problems can cause high superheat.
Q4: What causes low superheat?
A: Overcharge of refrigerant, faulty metering device, or evaporator fan problems can result in low superheat.
Q5: Why is superheat important for compressor life?
A: Proper superheat ensures only vapor enters the compressor, preventing liquid refrigerant from causing mechanical damage and oil dilution.